Template Title

Testing & Tagging

Test and Tag

Testing & tagging is mandatory in Bendigo to protect your staff and the public and to adhere to occupational health and safety guidelines (AS/NZS 3760). The owner or manager of a premises or business has a legal and ethical obligation to your staff and clients to provide regular appliance test and tagging. For testing time frames please refer to table at the bottom of this page.

To arrange for your electrical equipment to be tested & tagged call Electric Pro today on (03) 4444 2010 or

Arrange a Booking


test & tag Bendigo

Exit & Emergency Light Testing

Testing of your Exit & Emergency Light System is mandatory under your states building, fire and essential services code. All scheduled maintenance testing must be carried out at least twice per annum.

At each inspection Electric Pro perform the following:

  1. Operate the exit and emergency lighting systems from their battery supply and ensure that they remain illuminated for at least 90 minutes
  2. Replace any defective lamps
  3. Replace any defective batteries with the correct type
  4. Clean all signs in accordance with Australian Standard Guidelines
  5. Advise those responsible for the operation of equipment of any changes or adjustments
  6. Ensure that the Maintenance and Log Manual has been filled out and left in a secure place
Exit & Emergency Light Testing Bendigo

RCD Testing

A RCD (Residual Current Device) is a safety device that disconnects a circuit when it detects an imbalance of the electric current. The RCD turns the power off almost immediately to prevent electrocution. While you may still receive an electric shock, the duration will be very short, reducing the risk of serious injury.

Electric Pro will inspect and test your workplace Fixed and Portable RCD's in accordance with AS/NZS 3760:2010 and state based legislation.  A simple Operating Time Test will be conducted to ensure your RCD trips the power within the recommended time frame. You will then receive a copy of all test results.

Contact Electric Pro today if you require RCDs tested by one of our licenced electricians.

RCD testing Bendigo

Type of Environment and/or Equipment Interval Between Inspection and Tests for Appliance Test Tag Cord Extension Sets and EPODs
Class of Equipment Residual Current Devices (RCDs)
Class 1 – protectively earthed equipment Class 2 – double insulated equipment Push-button test by user Operating Time test
Portable Fixed Portable Fixed
Factories, workshops, places of work or repair, manufacturing, assembly, maintenance or fabrication 6 months 12 months Daily or before every use 6 months 12 months 12 months 6 months
Laboratories, healthcare and educational establishments, tea rooms and office kitchens 12 months 12 months 3 months or before every use 6 months 2 years 2 years 12 months
Office environment: When the equipment or supply flexible cord is subject to flexing in normal use OR is open to abuse OR is in a hostile environment 12 months 12 months 3 months 6 months 2 years 2 years 12 months
Office environment: When the equipment or supply flexible cord is NOT subject to flexing in normal use and is NOT open to abuse and is NOT in a hostile environment 5 years 5 years 3 months 6 months 2 years 2 years 5 years
Hire equipment Inspect before each hire, test monthly Inspect before each hire, test monthly Prior to each hire or monthly N/A Prior to each hire or monthly N/A Inspect before each hire, test monthly
Repaired/serviced/second hand equipment After repair or service which could affect electrical safety or on introduction to service
Equipment used for commercial cleaning 6 months 12 months 3 months N/A 2 years N/A 6 months
Residential 2 years 2 years 6 months 6 months 2 years 2 years 2 years